Nuclear Grade Cable Application Range
- Dec 19, 2018 -

· This product is suitable for the control and signal connection cables used in the control system network with the rated voltage Uo/U of the nuclear power plant Uo/U.

• The cable conductor allows a long-term operating temperature of 90 ° C, the maximum temperature of the cable conductor does not exceed 250 ° C during short circuit, and the duration does not exceed 5 seconds.

• The ambient temperature when laying the cable should not be lower than 0 °C.

· Allowable bending radius when laying cables:

— cable without armor should be no less than 6 times the diameter of the cable

— Cables with armor or copper tape shielding results should be no less than 12 times the cable diameter

— Flexible cables with a shield structure should be no less than 6 times the diameter of the cable.

· When the conductor is allowed to work at a temperature of not more than 90 ° C for a long time, the identification life of the cable is not less than 40 years.

· The finished cable should meet the requirements of Class A bundle burning test specified in GB/T18380.3.

· Finished cable smoke density: light transmittance is not less than 70%.

· Radiation resistance: 25 × 104Gy

• Halogen-free: When the non-metallic material is burning, the acidity of the evolved gas (expressed as PH value) should be greater than 4.3; the conductivity is not more than 10 μS/mm.

Bare wire and bare conductor products

The main features of this product are: pure conductor metal, no insulation and sheath layer, such as steel core aluminum stranded wire, copper-aluminum busbar, electric locomotive line, etc.; processing technology is mainly pressure processing, such as smelting, rolling, pulling System, stranding/tightening stranding, etc.; products are mainly used in suburbs, rural areas, user main lines, switch cabinets, etc.